Thermocouple Cables
single pair multipair more

 Telecommunication cables


Auxiliary Multipair Cables - ARMOUR SCREEN LSZH

Description

Copper, Multi Pair, XLPE-Insulation, Collective, Armour, LSZH Sheath

Application

These light current control cables are intended primarily for use with control, indication and alarm equipment for

switchgear and similar power apparatus in power stations and substations. Suitable for use on circuits where

the nominal voltage does not exceed 150V d.c. or 110V a.c. Suitable for direct buried applications.

Standard

ENATS 09-6 ISSUE 9

Cable Construction

Conductors : Solid (Class 1) tinned copper conductors to BS EN 60228.

Insulation : XLPE insulation to BS7655.

Pair Identification : See colour code.

Binder Tape : p.e.t.p. tape of suitable overlap.

Collective Screen : tinned copper drain wire under and in contact with aluminium/p.e.t.p. laminated tape applied

metallic side down.

Inner Sheath : LSZH inner sheath to BS7655.

Armouring : Mild galvanised steel wires to BS EN10257-1.

Outer Sheath : Black LSZH outer sheath to BS7655.

Voltage Rating : 150V d.c./110V a.c.

Temperature Rating : 70°C maximum conductor operating temperature.

Electrical data @ 20ºC


Conductor size

Nom

mm²

0,5

Conductor resistance

Solid / Class 1

Max

Ω/km

36

Insulation resistance

Individual conductor

Min.

MΩxkm

80

Screen and armour

Min.

MΩxkm

1

Mutual capacitance 1kHz

core to core

Max.

nF/km

150

Mutual inductance

Max.

µH/Ω

50

Test voltage

Ums core: core

V

2000

Ums core: armour

V

2000

Properties for cable


Code Colour

ENATS 09-6 Issue 9 * Table 1

Fire Resistant

N.A.

Flame Retardant

IEC 60332-3-22

Low Smoke Emision

IEC 61034-1-2 > 60%

Other Properties

 

Minimum Bending Radius

10 X O.D.

Properties for outer sheath


Limiting Oxygen Index

LOI > 30%

Amount of halogen acid gas

IEC 60754-1 HCl<0.1%

Oil Resistance

ANSI/ICEA S-73-532 (4h, 70ºC)

Sunlight Resistance

UL 1581 Section 1200

Temperature Installation

-15ºC/50ºC

Temperature Operating

-40ºC/50ºC

Construction Parameters


No. Pairs

Cores

RT Insulation Nominal

RT Inner sheath

Ø over inner sheath

Ø of armour wire nom.

RT of outer sheath nom.

Overall diameter

Weight approx.

 

mm²

mm

mm

mm

mm

mm

mm

kg/km

2

0.5mm²

0,3

0,8

5,37

0,9

1,3

9,77

201

5

0.5mm²

0,3

1,0

8,84

0,9

1,4

13,44

356

10

0.5mm²

0,3

1,1

11,56

1,25

1,5

17,06

597

20

0.5mm²

0,3

1,2

15,01

1,25

1,6

20,71

854

40

0.5mm²

0,3

1,4

23,96

1,6

1,8

30,76

1669

60

0.5mm²

0,3

1,6

25,94

1,6

2,0

33,14

2046

100

0.5mm²

0,3

1,9

32,28

2

2,2

40,68

3173

Code colour ENATS 09-6 Issue 9 Table 1
2 Pair Cable (quad)


1

White

Red

Blue

Orange

5 Pair Cables to 20 Pair Cables


1

White

Blue

11

Black

Blue

2

White

Orange

12

Black

Orange

3

White

Green

13

Black

Green

4

White

Brown

14

Black

Brown

5

White

Grey

15

Black

Grey

6

Red

Blue

16

Yellow

Blue

7

Red

Orange

17

Yellow

Orange

8

Red

Green

18

Yellow

Green

9

Red

Brown

19

Yellow

Brown

10

Red

Grey

20

Yellow

Grey

For 40 pairs cables – Pairs 1 to 20, two times
For 60 pairs cables – Pairs 1 to 20, three times
For 100 pairs cables – Pairs 1 to 20, five times